Program
|
Description
|
Selectable option
|
00
|
Exit setting mode
|
Escape(default)
|
One-button restore setting options
|
|
|
01
|
Output source priority: To configure load power source priority
|
Utility First
|
Utility will provide power to the loads as first priority.
Solar and battery energy will
provide power to the loads only when utility power is not available.
|
Solar first (default)
|
Solar energy provides power to
the loads as first priority.
If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time.
Battery provides power to the loads only when any one condition happens:
- Solar energy and utility is not
available.
- Solar energy is not sufficient and
utility is not available.
|
SBU priority
|
Solar energy provides power to
the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either low-level warning voltage
or the setting point in program 12.
|
02
|
maximum charging current: To configure total charging current for solar and utility chargers.
(Max. charging current = utility charging current + solar charging current)
|
|
|
|
|
|
60A(Default)
|
|
|
|
|
|
|
03
|
AC input voltage range
|
Appliances (default)
|
If selected, acceptable AC input voltage range will be within 90-280VAC
|
|
If selected, acceptable AC input voltage range will be within
170-280VAC.
|
05
|
Battery Type
|
AGM(Default) battery
|
Flooded battery
|
User-Defined
|
If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
|
User-Defined
|
When the solar energy exists,Set this item to LIB, and the lithium battery will be activated for 3 second.
|
06
|
Auto restart when overload occurs
|
Restart disable (default)
|
Restart enable
|
07
|
Auto restart when over temperature occurs
|
Restart disable (default)
|
Restart enable
|
09
|
Output frequency
|
50HZ Default
|
|
10
|
Output voltage
|
|
230V(Default)
|
|
|
11
|
Maximum utility charging
Current
Note: If setting value in program 02 is smaller than that in program in 11, the inverter will apply charging
current from program 02 for utility charger
|
|
|
|
30A(Default)
|
|
|
|
|
|
|
12
|
Setting voltage point back to utility source when selecting “SBU priority” Or “Solar first” in program 01.
|
Available options in 3.6KW model:
|
|
|
23.0V(default)
|
|
|
|
|
|
Available options in 6.2KW model:
|
|
|
46V (default)
|
|
|
|
|
|
13
|
Setting voltage point back to battery mode when selecting “SBU priority” or “Solar first” in program 01.
|
Available options in 3.6KW model:
|
Battery fully charged
|
|
|
|
|
|
|
27V(Default)
|
|
|
Available options in 6.2KW model:
|
Battery Fully Charged
|
|
|
|
|
|
|
54V(DEFAULT)
|
|
|
|
|
16
|
Charger source priority: To configure charger source priority
|
If this inverter/charger is working in Line, Standby or Fault mode,
charger source can be programmed as below:
|
Solar first
|
Solar energy will charge battery as first priority.
Utility will charge battery only
when solar energy is not available.
|
Solar and Utility (default)
|
Solar energy and utility will charge battery at the same time.
|
Only Solar
|
Solar energy will be the only
charger source no matter utility is available or not.
|
If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
|
18
|
Alarm control
|
Alarm on (default)
|
Alarm off
|
19
|
Auto return to default display screen
|
Return to default display
screen (default)
|
If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage
/output voltage) after no button is
pressed for 1 minute.
|
Stay at latest screen
|
If selected, the display screen will stay at latest screen user finally switches.
|
20
|
Backlight control
|
Backlight on (default)
|
Backlight off
|
|
22
|
Beeps while primary source is interrupted
|
Alarm on (default)
|
Alarm off
|
|
|
23
|
Overload bypass:
When enabled, the unit will transfer to line mode if overload occurs in battery mode.
|
Bypass disable (default)
|
Bypass enable
|
|
|
25
|
Record Fault code
|
Record enable (default)
|
Record disable
|
|
|
26
|
Bulk charging voltage (C.V voltage)
|
3.6KW default setting: 28.2V
|
|
|
6.2Kw default setting: 56.4V
|
|
|
If self-defined is selected in program 5, this program can be set up. Setting range is from 25.0V to 31.5V for 3.6KW model and
48.0V to 61.0V for 6.2xW model. Increment of each click is 0.1V.
|
|
|
27
|
Floating charging voltage
|
3.6KwdefauIt setting: 27.0V
|
|
|
6.2Kw default setting: 54.0V
|
|
|
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V for 3.6KW model and 48.0V to 61.0V for 6.2KW model. Increment of each click is 0.1V.
|
|
|
29
|
Low DC cut-off voltage
|
3.6Kw default setting: 20.0V
|
|
|
6.2Kw default setting: 40.0V
|
|
|
|
|
If self-defined is selected in program 5, this program can be set up. Setting range is from 20.0V to 24.0V for 3.6KW model and 40.0V to 48.0V fOf 6.2KW model. Increment of each click is 0.IV. Low DC cut-off voltage will be fixed to setting value no matter
what percentage of load is connected.
|
|
|
30
|
Battery equalization
|
Battery equalization
|
Battery equalization disable (default)
|
|
|
If“FIooded” or “User-Defined” is selected in program 05, this
program can be set up.
|
|
|
31
|
Battery equalization voltage
|
3.6KW default setting: 29.2V
|
|
|
6.2KW default setting: 58.4V
|
|
|
Setting range is from 25.0V to 31.5V foF 3.6KW model and 48.0V
to 61.0V fOF 6.2KW model. Increment of each click is 0.IV.
|
|
|
33
|
Battery equalized time
|
60min (default)
|
Setting range is from Smin to 900min. Increment of each click is Smin.
|
|
|
34
|
Battery equalized timeout
|
120min (default)
|
Setting range is from Smin to 900 min. Increment of each click is 5 min.
|
|
|
35
|
Equalization interval
|
30days (default)
|
Setting range is from 0 to 90 days. Increment of each click is 1 day
|
|
|
36
|
Equalization activated immediately
|
Enable
|
Disable (default)
|
|
|
If equalization function is enabled in program 30, this program can be set up. If “Enable” is selected in this program, it’s to activate battery equalization immediately and LCD main page will shows
“ “. If “Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on program 35
setting. At this time, “ ”will not be shown in LCD main page.
|
|
|
37
|
GRID-tie operation
|
Off grid (default)
|
Inverter operates only in off-grid
mode. Solar energy providespowerto the loads as first priority and charging
second
|
|
|
Hybrid
|
Inverter operates hybrid mode. Solar energy provides power to the loads as first priority and charging second
Excess energy feed to grid.
|
|
|
38
|
GRID-tie current
|
|
Increment of each click is 1A.
|
|
|
39
|
Led pattern light
|
LED Pattern OFF
|
LED Pattern ON(default)
|
|